The state-of-the-art air temperature sensor type 2033 is provided with a platinum resistance Pt 100, DIN 60751 B, 1/3 tolerance and four-wire connection. A five-meter measuring cable is also included.

This air temperature sensor in shelter is equipped with a protection shelter which is designed to protect the sensor from solar radiation and precipitation that induce a measurement error.

The shelter of this air temperature sensor is made up of single segments with the addition of a top cover which consists of an especial white plastic material.

Type 2033 – air temperature sensor is set in a plastic shaft and screwed into the base plate via a cable duct. There are two holes in the base plate. There’s a distance of 30 millimetres between them and you may use M8-screws to fasten the device.

Other than having a large number of advantages and benefits, the air temperature sensor in shelter offers an extensive range of applications in different industries including:

  • Pharmaceutical industries
  • Meteorological
  • Building services equipment
  • HVAC
  • Food industries

approx. ø 120 mm, height approx. 240 mm

max. 1.4 kg

1/3 tolerance, acc. to DIN 60751B, Platinum resistance Pt 100

4 x 0.5 mm2, length 5 m, LiY( C )Y

2 x 0.14 mm2, length 5 m, LiYY

12, approx. 70 mA (Versions 2033.1000, .1200 and .1300 only)

meas. Range –35 to +45 °C, adjustable, Pt 100

0 to 10 V, 4 to 20 mA, supply 10 to 35 V DC load depending (500 Ω to 1.9 kΩ lin.)

±0.25 %

Ambient temp.: < 50 ppm/°C, Supply voltage: < 50 ppm/V

EN 50081-1, EN 50082-2

-40 to +60 °C

8-p. Connector IP 67

  • Operating temperature: -40 °C to +60 °C
  • Measuring converter, input: Pt 100, meas. range –35 °C to +45 °C
  • Measuring converter, output: 4 mA to 20 mA or 0 V to 10 V, 10 V to 35 V DC load depending (500 Ω to 1,9 kΩ lin.)
  • Measuring converter, operating temperature: -40 °C to +60 °C
  • Error by ambient temperature: < 50 ppm/°C
  • Error by supply voltage: < 50 ppm/V
  • maximum Error: 25%